AC GROUNDING HiTESTER 3157

Description

Protective Ground Tester Indispensable for Standards Certification

Basic specifications

Accuracy guaranteed: 1 year

Basic functions AC 4-terminal method resistance measurement
Display Fluorescent tube (digital display)
Current setting range 3.0 A to 31.0 A AC (0.1 A resolution), into 0.1Ω load
Max. output power 130 VA (at output terminals)
Open-terminal voltage Max. 6 V AC
Generator frequency 50 Hz or 60 Hz sine wave (selectable)
Resistance measurement 0 to 1.800 Ω (0.001 Ω resolution), Accuracy: ±2% rdg. ±4 dgt. after zero-adjust
Voltage measurement 0 to 6.00 V AC (single range 0.01 V resolution), Accuracy: (1 % rdg. +5 dgt.)
Monitor section 0 to 35.0 A AC/ 0 to 6 V AC, Refresh rate: 2 times/s
Timer display Counts down time after start until preset time, Shows elapsed time after start
Timer setting 0.5 s to 999 s
Comparator PASS/FAIL evaluation using preset upper/lower limit, buzzer sound, signal output
Memory function Max. 20 settings (with save/load)
Interfaces EXT I/O, EXT SW, GP-IB or RS-232C (option)
Power supply 100 to 120 V/200 to 240 V AC (switching, 50/60 Hz)
Dimensions and mass 320 mm (12.60 in)W × 90 mm (3.54 in)H × 263 mm (10.35 in)D, 7 kg (246.9 oz)
Included accessories Power cord ×1, Instruction Manual ×1, Spare fuse (inlet) ×1, Shorting bar ×2