High-precision Current Testing
Accuracy guaranteed: 1 year
Rated current | 1000 A AC/DC | |||||
---|---|---|---|---|---|---|
Frequency bandwidth | DC to 100 kHz | |||||
Diameter of measurable conductors | Max. φ 50 mm (1.97 in.) | |||||
Max. allowable input | ±1900 Apeak (Within 20 ms in an environment of 40°C/104°F or less) |
|||||
Output voltage | 2 mV/A | |||||
Output resistance | 50 Ω ± 10 Ω | |||||
Accuracy (amplitude) ±(% of reading + % of full scale) |
DC: 0.2% + 0.02% DC < f ≤ 100 Hz: 0.2% + 0.01% |
|||||
Linearity | ±20 ppm Typical | |||||
Common-Mode Voltage Rejection Ratio (CMRR) |
DC to 1 kHz:150 dB or greater 1 kHz to 10kHz:130 dB or greater 10 kHz to 50 kHz:100 dB or greater (effect on output voltage and common mode voltage) |
|||||
Automatic phase correction | Automatically performs phase correction when connected to PW8001 | |||||
Operating temperature, humidity | -40°C to 85°C (-40°F to 185°F), 80% RH or less | |||||
Standards | Safety IEC 61010-2-032:2012/EN 61010-2-032:2012 Type D EMC IEC 61326-1:2012/EN 61326-1:2013 |
|||||
Withstand voltage | AC 4,260 V | |||||
Power supply | Power suppled via the Power Analyzer PW8001, PW6001, PW3390, Sensor Unit CT9555, CT9556, CT9557, or 3CH CURRENT UNIT U8977 | |||||
Max. rated power | 7 VA or less (When measuring 1000 A/55 Hz with ±12 V power supply) | |||||
Dimensions and mass | Approx. 238 mm W × 116 mm H × 35 mm D (approx. 9.37 in. W × 4.57 in. H × 1.38 in. D), 990 g |
|||||
Cable length | Approx. 3 m (9.84 ft.) | |||||
Included accessories | ・Markup bands(×6) ・Carrying case ・Instruction manual |